Earth Fault Test - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Earth fault test

Earth fault tests should be carried at this stage:
0V (-ve)
LINE
EARTH
FAULT
TEST
L1
0V-line earth fault test
¨
Connect the 0V line to the earth of the control panel
enclosure. This may have to be sustained for up to
1 minute for the fault to be detected. The display
should show:
Earth Fault
¨
Restore normal conditions. The display show:
Earth Fault cleared
+ve line earth fault test
¨
Now connect the +ve line to earth via a 10K ohm
resistor. This may have to be sustained for up to
1 minute for the fault to be detected. The display
shows an Earth fault message as above and after
restoration a cleared message.
"
If the resistance between Earth and Loop +ve
is in the order of a few ohms then this will be registered
as a 'short circuit'.
Type of earth fault
Interrogate the [PSU] readings in the [Test/Eng] menu to
establish the type of Earth fault.
Type of Earth fault
No earth fault
+ve line and earth
-ve line and earth
¨
At the end of the test operate the [Repair] function at
the panel.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
MICC CABLE
PANEL
enclosure
BOARD
BOARD
TERMINALS
0V
Earth (Ear) reading
around 60
greater than 75
less than 40
Vigilon (EN & BS) Compact (VA) panels
L1 (+ve)
LINE
EARTH
FAULT
TEST
10K
resistor
L1
0V
49