Generic Commissioning instructions

Printer paper roll

"
The printer paper roll is secured with an elastic
band to the card guide on the inner door.
Remove the paper roll from the card guide and install paper.
Ensure the paper roll enters the printer mechanism as shown .
Door
Printer
mechanism
Paper
&
feed knob
On the outside of the inner door there is a paper
feed knob, DO NOT turn the knob in an upwards
direction as this may damage the integral printer.
Upon completion of all commissioning work a new paper roll
should be fitted.

Setting the DKC card

The link, switch and pot on the DKC are factory configured as
shown in below. The switch can be reconfigured for required
baud rate and domain address.
DKC ASSEMBLY
Danger
WARNING
REMOVAL OF COVER
EXPOSES HIGH V
H VOLTAGES
Inner door assembly
Leave this link connected
The link is used to bypass
a keyswitch not used
on this product
Factory set link position:
Control buttons active
Control buttons are active
Control buttons:
Sound alarms button
Silence alarms button
Reset button
Verify button
Control buttons are inactive
or
Baud Rate
Domain address
2
Baud 3
1
4
Off Off 1200
Off Off Off Off Off Off 64
Off On 2400
Off Off Off Off Off On 1
On Off 9600
Off Off Off Off On Off 2
On On 19200
On On On On On Off 62
On On On On On On 63
Factory set domain address - 1 with 19200
baud (SHADED)
18
Paper
roll
Fold paper end thus
before attempting to
feed it through printer
SW1
8
7
6
5
4
3
2
1
OFF
ON
P6
P2
5
6
7
8
Addr.
etc

Card installation

&
When installing the cards into a backplane
always use anti-static work procedures. DO NOT use
anti-static procedures on live equipment.
"
An IO Card is not required for connection to
DKC and Commissioning tool. The DKC now connects
directly to the new MCC card and the Commissioning tool
is connected via the USB on MCB.
The two ribbon cables held together under a masking tape on the
DKC assembly must be routed into the backbox and connected
to the Master Controller Card.
"
Ensure the ribbon cable is secured under a
clamp on the backplane and then plug the master
controller card before the card is fitted to the backplane.
Backplane
40 way ribbon
20 way ribbon
Master Controller Card (MCC)
to be fitted to socket
P1 CARD 0 on backplane
P1
CARD 0
P2
CARD15
P3
CARD 1
P4
CARD 2
P5
CARD 3
P6
CARD 4
P7
CARD 5
P8
CARD 6
Backplane
&
Always ensure the panel is completely
powered down before removal or fitting of cards into
the backplane. Power down the battery supply
before the mains supply. The power up should be
done in a reverse order.
¨
Ensure all the cards are installed in the correct location
in the backplane and are firmly seated in their
respective slots.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Secure the two ribbon
cables (at the fold) under the clamp
located on the backplane
Card guides
Use the USB port on
the MCC to connect to
the Commissioning tool.
Main Controller Card or
Local Controller Card (SUPPLIED)
Network or IO Card (Optional)
Loop Processor Card (SUPPLIED)
or RS232
Loop Processor Card or RS232
(Option)
Loop Processor Card or RS232
(Option)
Loop Processor Card or RS232
(Option)
Network or RS232 or
Loop Card#
Network or RS232 or
Loop Card#
# for VIG1-72 only