Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 170

For the fire alarm systems
Table of Contents

Advertisement

Interface and panel outstations
Rotary
switch
(S5)
setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Other
manufacturers
MCP
IO Line tests
NOTE: All input circuits must have a GENT End-of-line units fitted,
irrespective of manufacture of detector.
detector
detector range
manufacturer
Gent
XEN-DET-XXXrange
Hochiki or
CD range
Apollo
Series 20
Menvier
Series 700
Nittan
NH-G Series
Notifier
EC range
Thorn
Series 300
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
Gent
XEN-DET-XXX range
NOTE: On changing the rotary switch setting, the interface unit must be
completely powered-down, both mains and battery supply, and then
powered-up again.
Also the loop on which the unit resides must be reallocated.
q Where an input circuit is required to have other manufacturers
manual call points, then a 3.9V zener diode should be fitted in series
with the contacts of the call point. There should be no other
components fitted to the call point contacts.
NOTE: Where NITTAN detectors and manual call point are installed on
input circuit, the Vigilon system will not be able to differentiate between a
fire from a call point or detector.
q Test the IO line as per project specification. The tests should be based
on the type of equipment interfaced, for example the interface may
control air conditioning system, escalator, fire door release or sprinkler
system.
VIG-INT-MAINS - Mains powered interface
comment
Without
resistor fitted
to detector
base
Vigilon Sys tem Com mis sioning
link LK1
type of
on
detectors
interface
tested
board
1-2
whole range
1-2
optical and
heat
1-2
optical
1-2
Heat
1-2
Heat
2-3
Optical
1-2
whole range
1-2
whole range
1-2
whole range
1-2
whole range
1-2
whole range
1-2
whole range
1-2
whole range
1-2
whole range
1-2
whole range
1-2
whole range