3: I/O Point Control; Earth Fault Resistance - Honeywell SILENT KNIGHT 6700 Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Testing and Troubleshooting
6.
Press the left arrow key to exit the SLC multi-locater function.
NOTE: The system will resume normal operation once you exit SLC Device Locater.
11.3.3 I/O Point Control
This feature allows you to toggle any output on or off and trip any input device. This option can be useful to test a point's output mapping.
I/O Point Control can only be accessed if enabled in the user profile.
Follow these steps to control an I/O point:
1.
From the Main Menu, select 2 (Point Functions).
2.
Select 6 (I/O Point Control).
3.
Select the module the point is on.
4.
Enter the point number, or press the up or down arrow key to select the point you want to test, and then press ENTER.
5.
Press ENTER to generate an alarm for an input point or activate an output point.
6.
To exit, press the left arrow key.

11.4 Earth Fault Resistance

Table 11.2 lists the Earth Fault Resistance Detection for each applicable terminal on the FACP.
NAC 1 -
NAC 1 +
NAC 2 -
NAC 2 +
SBUS -
SBUS +
SBUS A
SBUS B
SLC IN -
SLC IN +
SLC OUT -
SLC OUT +
116
TERMINAL
(values in kohms)
high trip
0
0
0
0
0
Table 11.2 Earth Fault Resistance
LOW BIASED
high restore
0
0
0
0
0
0
0
0
0
0
0
0
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Earth Fault Resistance
HIGH BIASED
low trip
low restore
0
0
0
0
0
0
0