Parameter Data Record; Dependencies When Configuring With Gsd File - Siemens SIMATIC ET 200SP Manual

Analog input module ai 8xrtd/tc 2-wire hf 6es7134-6es7134-6jf00-0ca1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter data record

A.1

Dependencies when configuring with GSD file

When configuring the module with a GSD file, remember that the settings of some
parameters are dependent on each other.
Configuring with a PROFINET GSD file
The table lists the properties and their dependencies on the measurement type and
measuring range for PROFINET.
Table A- 1
Dependencies of the measurement type / measuring range
Measure-
Measuring range
ment type
Deactivated
*
Voltage
±50 mV, ±80 mV,
±250 mV, ±1 V
Resistor
150 Ω, 300 Ω,
600 Ω, 3 kΩ, 6 kΩ
Resistor
PTC
Thermal
Pt100 climatic
resistor
Pt200
Pt500
Pt1000 climatic
Ni100
Ni120
Ni200
Ni500
Ni1000 climatic
LG-Ni 1000 climatic
52
Temperature coef-
Reference junction
ficient
*
*
*
*
*
*
*
*
Pt 0.00385055
Reference channel
Pt 0.003916
of group 0, 1, 2, 3
Pt 0.003902
No reference chan-
Pt 0.00392
nel mode
Pt 0.00385
No reference chan-
nel mode
Ni 0.00618
Ni 0.00672
LG-Ni 0.005
Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1)
Temperature unit
Conductor re-
sistance
*
*
*
*
*
x
*
*
Degrees Celsius
x
Degrees Celsius
Degrees Fahrenheit
Degrees Celsius
Degrees Fahrenheit
Manual, 09/2018, A5E32942580-AB