Commissioning and Diagnostics
STEP 7 Version 5.1, Service Pack 2, Hotfix 1 or higher and optional package SIMATIC PDM
How to set
1.
Double-click on the DP slave "IM 151-2" in HW Config (in the upper part of the
parameters for
station window). Select "Specialist" in the next window. Result: SIMATIC PDM is
all modules of
started and all modules of the ET 200iS are loaded.
the ET 200iS
2.
Upload all parameters of the modules (menu command File > Full Upload to
PG/PC ).
3.
Set the parameters for all required modules. In the left-hand pane of the SIMATIC
PDM window, you can select all the modules of the ET 200iS.
4.
Save the changes (menu command File > Save) so that the file is updated.
5.
Download all parameters to the modules (menu command Device > Full
Download to Device). Close SIMATIC PDM.
Setting Parameters with SIMATIC PDM (stand-alone version)
The following table describes the most important steps in parameter assignment:
Table 7-6

Setting Parameters with SIMATIC PDM

SIMATIC PDM Version 5.1, Service Pack 2 or higher (stand-alone version)
Characteristics
You set the parameters for the ET 200iS.
Requirements
The required software has been installed on the PG/ PC or PCS7-ES.
To work with PDM online, you require a PROFIBUS-DP interface, for example CP
5611 (6GK1 561-1AA00). The CP must be set to the PROFIBUS-DP interface (in
the SIMATIC Manager: menu command Options > Set PG/PC Interface).
How to set
1.
Start the SIMATIC Manager.
parameters for
2.
Select the process device network view as the standard view with the menu
the electronics
command Options > Settings > View > Process Network View.
modules
3.
Create a new project with the menu command File > New. The "New" dialog
opens in which you enter the required project name and confirm with "OK".
4.
Now select the Networks icon, right-click and select Insert New Object > PC and
Insert New Object > PROFIBUS DP Network
5.
In the left-hand pane of the window, select the PC icon. An icon labeled DP
Interface now appears in the right-hand pane of the window. Right-click on this
icon and select "Object Properties". In the next dialog, select "PROFIBUS-DP
Networks" under networks and confirm with "OK".
7-8
Version 5.1, Service Pack 2 or higher
or
PCS 7 Version 5.2 or higher
ET 200iS Distributed I/O Station