Checking The Location Of The Hot Gas Baffle Plates; Preparing The Heating System For Operation - Buderus Logano GB125 Installation And Maintenance Instructions Manual

Oil condensing boilers with logatop be burner
Hide thumbs Also See for Logano GB125:
Table of Contents

Advertisement

8.2

Checking the location of the hot gas baffle plates

Prior to commissioning check that the hot gas baffle pla-
tes are horizontally positioned.
B Pull the power plug from the SAFe.
B Open the burner door by removing the two hexagon
side bolts.
B Slightly pull the hot gas baffle plates out of the hot
gas flues.
BOILER DAMAGE
Never remove or reposition the hot gas
baffle plates.
B Position the hot gas baffle plates horizontally and
push them into the hot gas flues.
B Close the burner door and secure with the two hexa-
gon bolts (tighten to approx. 10 Nm). Tighten the he-
xagon bolts evenly to properly seal the burner door.
B Attach the power plug to the SAFe.
8.3
Preparing the heating system for
operation
B Turn on the fuel supply at the main shut-off valve.
B Switch on the heating system emergency stop switch
(if installed) and/or insert/set the corresponding do-
mestic fuse/circuit breaker.
Logano GB125 oil condensing boiler - Technical specifications are subject to change without prior notice.
Commissioning the heating system
1
Fig. 36 Opening the burner door
1
Hot gas baffle plates in the hot gas flues
8
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents