Fit The Concentric Balanced Flue Outlet For Balanced Flue Operation (Accessory) - Buderus Logano GB125 Installation And Maintenance Instructions Manual

Oil condensing boilers with logatop be burner
Hide thumbs Also See for Logano GB125:
Table of Contents

Advertisement

7.2
Fit the concentric balanced flue outlet for balanced flue
operation (accessory)
If you are using a concentric ventilation air and flue gas
pipe, you must fit a concentric balanced flue outlet.
Only to be used with installation types OC
RISK TO LIFE
through poisoning.
B To avoid flue gas escaping, ensure that
the height of the condensed water di-
scharge is not less than 100 mm.
B Push the concentric balanced flue outlet into the fem.
connection of the condensate pan and secure to the
back panel of the boiler.
B Using a clip, fasten combustion air hose to the con-
centric balanced flue outlet.
USER INFORMATION
Route the flue with a slope of at least 3° to-
wards the boiler to ensure that any con-
densate is reliably drained via the boiler
condensate drain.
Logano GB125 oil condensing boiler - Technical specifications are subject to change without prior notice.
and OC
.
13x
33x
Fig. 18 Fitting balanced flue outlet
1
2
3
4
Fig. 19 Flue gas pipe
Installing the boiler
1
Combustion air hose
Concentric balanced flue outlet
Ventilation air test port
Flue gas test port
7
3
4
2
7 747 011 453-18.1RS