Troubleshooting by Indication on the Remote Controller
" J2 "
2.24
Current Sensor Malfunction
J2
Remote
Controller
Display
Applicable
RXYQ5~48M
Models
Method of
Malfunction is detected according to the current value detected by current sensor.
Malfunction
Detection
Malfunction
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
standard compressor operation.
Decision
Conditions
!
Supposed
!
Causes
Troubleshooting
184
Faulty current sensor
Faulty outdoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Is the
connector for
current sensor
connected to X30A, X31A
on outdoor unit
PC board
(A1P)?
YES
Is the
current sensor
mounted on the T-phase
wire?
YES
NO
NO
Si39-302
Connect the connector, and
operate unit again.
Mount the current sensor
correctly, and operate unit again.
Replace current sensor and
outdoor unit PC board.