Pump Down Residual Operation - Daikin RXSQ24TAVJU Service Manual

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

SiUS331708EA
3.4

Pump Down Residual Operation

When activating the compressor, if liquid refrigerant remains in the evaporator, the liquid enters the compressor
and dilutes oil therein resulting in a decrease in lubricity.
Therefore, pump down residual operation is performed to collect refrigerant in the evaporator when the
compressor is stopped.
3.4.1 Pump Down Residual Operation in Cooling
Outdoor unit actuator
Compressor
Outdoor fan
Four way valve
Main electronic expansion
valve
Subcooling electronic
expansion valve
Hot gas bypass valve
Injection valve
Ending conditions
3.4.2 Pump Down Residual Operation in Heating
Outdoor unit actuator
Compressor
Outdoor fan
Four way valve
Main electronic expansion
valve
Subcooling electronic
expansion valve
Hot gas bypass valve
Injection valve
Ending conditions
Functions and Control
Electric symbol
24/36 class 48 class 60 class
STEP 18 load (24/36 class)
M1C
M1C
M1C
58 rps (48/60 class)
M1F,
M1F
M1F
Fan control
M2F
Y1S
Y1S
Y1S
OFF
Y1E
Y1E
Y1E
480 pulse (Fully open)
Y3E
0 pulse
Y2S
OFF
Y3S
Y3S
OFF
2 seconds
Electric symbol
24/36 class 48 class 60 class
STEP 18 load (24/36 class)
M1C
M1C
M1C
STEP 9 load (48/60 class)
M1F,
M1F
M1F
STEP 7
M2F
Y1S
Y1S
Y1S
ON
Y1E
Y1E
Y1E
0 pulse
Y3E
0 pulse
Y2S
OFF
Y3S
Y3S
OFF
4 seconds (24/36 class)
Up to 3 minutes (48/60 class)
Pump down residual operation:
Step 1
Pump down residual operation
Special Control
Pump down residual operation:
Step 2
STEP 6 load (24/36 class)
24 rps (48/60 class)
Fan control
OFF
240 pulse (Half open) (24/36 class)
480 pulse (Fully open) (48/60 class)
0 pulse
OFF
OFF
2 seconds
50