Mitsubishi Electric FR-F820-00046 Instruction Manual page 622

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

Pulse train
output (FM
type inverter)
For
Current output
indication
(CA type
on external
inverter)
meters
Voltage output
Status
monitoring
Operation
panel (FR-
DU08)
Fault type
Fault
Protective
function
Alarm,
Warning, Error
message
Surrounding air temperature
Surrounding air humidity
*4
Storage temperature
Ambience
Altitude/vibration
*1
The function is available for standard structure models and IP55 compatible models.
*2
Not activated in the inverter in the initial state.
*3
Available only for the IP55 compatible model.
*4
Applicable to conditions for a short time, for example, in transit.
2
*5
2.9 m/s
or less for the FR-F840-04320(185K) or higher.
Max. 2.4 kHz via one terminal (for the indication of inverter output frequency).
The item for monitoring can be changed using Pr.54 FM/CA terminal function selection.
Max. 20 mADC via one terminal (for the indication of inverter output frequency).
The item for monitoring can be changed using Pr.54 FM/CA terminal function selection.
Max. 10 VDC via one terminal (for the indication of inverter output frequency).
The item for monitoring can be changed using Pr.158 AM terminal function selection.
Output frequency, output current, output voltage, and frequency setting value are monitored.
The item for monitoring can be changed using Pr.52 Operation panel main monitor selection.
When a protective function is activated, a fault indication is displayed and the output voltage, output
current, output frequency, cumulative energization time, date (year, month, day) and time at the
occurrence of the fault are stored. Each fault is recorded and the last 8 records can be displayed.
Overcurrent trip during acceleration, Overcurrent trip during constant speed, Overcurrent trip during
deceleration or stop, Regenerative overvoltage trip during acceleration, Regenerative overvoltage trip
during constant speed, Regenerative overvoltage trip during deceleration or stop, Inverter overload
trip (electronic thermal relay function), Motor overload trip (electronic thermal relay function), Heatsink
overheat, Instantaneous power failure
*2
Loss of synchronism detection
earth (ground) fault overcurrent, Output short circuit, Output phase loss, External thermal relay
*2
operation
, PTC thermistor operation
device fault, PU disconnection, Retry count excess
circuit/RS-485 terminals power supply short circuit, 24 VDC power fault, Abnormal output current
*2
detection
, Inrush current limit circuit fault
communication fault, Safety circuit fault, Overspeed occurrence
*2
PID signal fault
, Internal circuit fault, User definition error by the PLC function, Abnormal internal
*3
temperature
Fan alarm, Stall prevention (overcurrent), Stall prevention (overvoltage), Electronic thermal relay
function pre-alarm, PU stop, Parameter copy, Safety stop, Maintenance signal output
*2
error, Operation panel lock
, Password locked
external power supply operation, Load fault warning, Emergency drive in operation
operation during communication fault
-10 to +50°C (non-freezing) (LD rating)
-10 to +40°C (non-freezing) (SLD rating, IP55 compatible models)
95% RH or less (non-condensing) (With circuit board coating (conforming to IEC 60721-3-3 3C2/3S2),
IP55 compatible models)
90% RH or less (non-condensing) (Without circuit board coating)
-20 to +65°C
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
2500 m or less (For the installation at an altitude above 1000 m, consider a 3% reduction in the rated
current per 500 m increase in altitude.) 5.9 m/s
*1
*1
, Undervoltage
, Input phase loss
, Upper limit fault detection, Lower limit fault detection, Output side
*2
, Option fault, Communication option fault, Parameter storage
*2
, CPU fault, Operation panel power supply short
*1
, Communication fault (inverter), Analog input fault, USB
*2
*2
, Parameter write error, Copy operation error, 24 V
*2
*3
, Internal fan alarm
2
*5
or less
at 10 to 55 Hz (directions of X, Y, Z axes)
*1*2
, Stall prevention stop,
, 4 mA input fault, Pre-charge fault,
*2
, USB host
*1
, Continuous
8. SPECIFICATIONS
8.3 Common specifications
1
2
3
4
5
6
7
8
9
10