 Enabling display of negative numbers during monitoring (Pr.290)
• Negative signal outputs can be selected for the items monitored via terminal AM (analog voltage output), via a
communication option, and on the operation panel. To check which items can be monitored with indication of negative
numbers, refer to the monitor items list (on
Pr.290 setting
0 (initial value)
1
2
3
4
5
6
7
—: Negative numbers indication disabled (positive only)
• Select the item group to enable the indication of negative signed numbers by setting Pr.1018 Monitor with sign selection.
Monitor item
Output frequency
Motor speed
Motor torque
PID deviation
BACnet terminal AM output level
Remote output 1
Remote output 2
Remote output 3
Remote output 4
PID manipulated amount
Second PID deviation
Second PID manipulated amount
Control circuit temperature
○: Negative numbers displayed with minus sign, —: Negative numbers not displayed (positive only)
*1
Negative numbers are not displayed on the operation panel. Confirm the rotation direction with the [FWD] or [REV] indicator.
NOTE
• When the output via terminal AM (analog voltage output) is set to "Negative numbers indication enabled", the output is within
the range of -10 to +10 VDC. Connect the meter with which output level is matched.
• Parameter unit (FR-PU07) displays only positive values.
 Monitor filter (Pr.1106 to Pr.1108)
• The response level (filter time constant) of the following monitor indicators can be adjusted. Increase the setting when a
monitor indicator is unstable, for example.
Pr.
Monitor number
7
17
1106
32
33
1107
6
1108
18
Parameters referred to
Pr.30 Regenerative function
Pr.37 Speed display, Pr.144 Speed setting
Pr.55 Frequency monitoring reference, Pr.56 Current monitoring reference, Pr.866 Torque monitoring
296
5. PARAMETERS
5.8 (M) Item and output signal for monitoring
page
Negative numbers
indication (via terminal AM)
Enabled
Enabled
Enabled
Enabled
Monitor indicator name
Motor torque
Load meter
Torque command
Torque current command
Motor speed
Motor excitation current
selectionpage 539
switchoverpage 286
289).
Negative numbers
indication on operation
panel
Enabled
Enabled
Enabled
Enabled
Pr.1018 setting
9999
0
*1
*1
Negative numbers indication (via
communication option)
Enabled
Enabled
Enabled
Enabled
referencepage 297