Mitsubishi Electric FR-F820-00046 Instruction Manual page 344

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

 Adjustment by selecting the voltage (current) at the bias/gain frequency without applying
voltage (current) between terminals 2 and 5 (4 and 5) (Example of adjustment at the gain
frequency)
Operating procedure
1.
Turning ON the power of the inverter
The operation panel is in the monitor mode.
2.
Changing the operation mode
Press
to choose the PU operation mode. The [PU] indicator turns ON.
3.
Selecting the parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
4.
Calibration parameter selection
Turn
until "
5.
Selecting a parameter
Turn
until "
"
" (C7 (Pr.905) Terminal 4 frequency setting gain) for terminal 4.
6.
Analog voltage (current) display
Press
to display the analog voltage (current) value (%) currently applied to terminal 2 (4).
7.
Analog voltage (current) adjustment
When
is turned, the gain voltage (current) value (%) currently set to the parameter appears.
Turn
until the desired gain voltage (current) value (%) appears.
8.
Setting completed
Press
to confirm the selection. The analog voltage (current) % and "
alternately.
• Turn
to read another parameter.
• Press
to return to the "
• Press
twice to show the next parameter.
NOTE
• Press
after step 6 to check the present bias/gain frequency setting. The setting cannot be checked after step 7.
" appears. Press
to display "
" (C4 (Pr.903) Terminal 2 frequency setting gain) appears for terminal 2, or
" display.
".
(
)" are displayed
5. PARAMETERS
5.9 (T) Multi-function input terminal parameters
1
2
3
4
5
6
7
8
9
10
343