• When the PID control mode is selected for emergency drive, the PID action during emergency drive operation is as follows
depending on the PID control setting.
Item
Measured value input selection
Forward action / reverse action
selection
Proportional band
Integral time
Differential time
Applied to the frequency /
calculation only
Other PID-related settings
• While the "retry" (Pr.523 = "22[], 32[]") is selected in the PID control mode, if a retry occurs at an occurrence of E.CPU,
E.1 to E.3, or E.5 to E.7 during emergency drive operation, the operation is performed not under PID control but with the
fixed frequency.
Use Pr.1013 Emergency drive running speed after retry reset to set the fixed frequency.
NOTE
• Refer to
page 401
 Operation of protective functions during emergency drive
• Operation of protective functions during emergency drive is as follows.
Protective
Operation during
function
emergency drive
E.OC1
Retry
E.OC2
Retry
E.OC3
Retry
E.OV1
Retry
E.OV2
Retry
E.OV3
Retry
E.THT
Retry
E.THM
Retry
E.FIN
Retry
E.IPF
The function is disabled.
E.UVT
The function is disabled.
E.ILF
The function is disabled.
E.OLT
Retry
E.SOT
Retry
E.LUP
The function is disabled.
E.LDN
The function is disabled.
E.BE
*1
Retry
E.GF
Retry
E.LF
The function is disabled.
*1
While the switchover to the commercial power supply operation during emergency drive operation is enabled, when the same protective function
is activated twice consecutively, the retry is attempted up to twice.
• The fault output during emergency drive operation is as follows.
Pr.190 to Pr.196 setting
Signal
Positive
logic
ALM
99
ALM3
66
Set point / measured value
input setting
Held
Held
Held
Held
Held
Applied to the frequency
Held
for details of PID control.
Protective
function
E.OHT
E.PTC
E.OPT
E.OP1
E.OP2
E.OP3
E.16
E.17
E.18
E.19
E.20
E.PE
E.PUE
E.RET
E.PE2
E.CPU
E.CTE
E.P24
Negative
logic
Turns ON at the occurrence of a fault that causes the above-mentioned "retry" or "output
199
shutoff" during emergency drive operation.
Outputted when a fault occurs during emergency drive operation.
166
During emergency drive operation, if a fault that does not activate any protective function
occurs, the signal turns ON for 3 s and then turns OFF.
PID control action
Deviation input setting
Terminal 4 input
Held
Held
Held
Held
Applied to the frequency
Held
Operation during
emergency drive
Retry
Retry
The function is disabled.
The function is disabled.
The function is disabled.
The function is disabled.
The function is disabled.
The function is disabled.
The function is disabled.
The function is disabled.
The function is disabled.
Output shutoff
The function is disabled.
Output shutoff
Output shutoff
Retry
The function is disabled.
The function is disabled.
Description
Without PID control setting
Terminal 4 input
Reverse action (initial setting)
100% (initial value)
1 s (initial setting)
Not used (initial setting)
Applied to the frequency
Held
Protective
Operation during
function
emergency drive
E.CDO
Retry
E.IOH
Output shutoff
E.SER
The function is disabled.
E.AIE
The function is disabled.
E.USB
The function is disabled.
E.SAF
*1
Retry
E.PBT
*1
Retry
E.OS
The function is disabled.
E.LCI
The function is disabled.
E.PCH
The function is disabled.
E.PID
The function is disabled.
E.1
Retry
E.2
Retry
E.3
Retry
E.5
Retry
E.6
*1
Retry
E.7
*1
Retry
*1
E.13
Retry
5. PARAMETERS
5.7 (H) Protective function parameter
1
2
3
4
5
6
7
8
9
10
269

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents