 Motor parameter initialization for PM motor control (Pr.998)
• Use PM parameter initialization to set the parameters required for driving an IPM motor MM-EFS or MM-THE4.
• The offline auto tuning enables the operation with an IPM motor other than the MM-EFS or MM-THE4 and with SPM
motors.
• Two methods of the motor parameter initialization are available for the use of MM-EFS or MM-THE4 motor; using Pr.998
PM parameter initialization, and using IPM initialization (
Initial
Pr.
Name
value
998
PM parameter
0
E430
initialization
*1
The setting is available for the standard structure model or the separated converter type.
• To use a motor capacity that is one rank lower than the inverter capacity, set Pr.80 Motor capacity before performing PM
parameter initialization.
• When "12, 14, 8009, or 9009" is set in Pr.998, the motor speed which was set/monitored in frequencies is set/monitored
in motor rotations per minute. To set/monitor in frequencies, set "112, 114, 8109, or 9109" in Pr.998.
• To change the setting of motor parameters for PM motor control to the setting required to drive an induction motor, set "0"
in Pr.998.
• When using an IPM motor other than the MM-EFS or MM-THE4 or an SPM motor, set "8009, 8109, 9009, or 9109" in
Pr.998.
Setting
range
Parameter setting (in frequencies) for an
0
induction motor
Parameter setting (in rotations per minute)
*1
for the IPM motor MM-EFS (1500 r/min
12
specification) or MM-THE4
Parameter setting (in rotations per minute)
*1
for the IPM motor MM-EFS (3000 r/min
14
specification)
Parameter setting (in frequencies) for the
*1
IPM motor MM-EFS (1500 r/min
112
specification) or MM-THE4
Parameter setting (in frequencies) for the
*1
IPM motor MM-EFS (3000 r/min
114
specification)
Parameter setting (in rotations per minute)
8009
for an IPM motor other than the MM-EFS or
MM-THE4 (after tuning)
Parameter setting (in frequencies) for an
8109
IPM motor other than the MM-EFS or MM-
THE4 (after tuning)
Parameter setting (in rotations per minute)
9009
for an SPM motor (after tuning)
Parameter setting (in frequencies) for an
9109
SPM motor (after tuning)
).
Description
The setting of the motor parameters is
changed to the setting required to drive an
induction motor.
The setting of the motor parameters is
changed to the setting required to drive an
IPM motor.
The setting of the motor parameters is
changed to the setting required to drive an
IPM motor. (Set Pr.71 Applied motor
and perform offline auto tuning in
advance. (Refer to
The setting of the motor parameters is
changed to the setting required to drive an
SPM motor. (Set Pr.71 Applied motor
and perform offline auto tuning in
advance. (Refer to
1
2
3
4
5
6
7
8
page
375.))