 Selecting the operation mode for power-ON (Pr.340)
• Depending on the Pr.79 and Pr.340 settings, the operation mode at power-ON (reset) changes as described below.
Pr.340
Pr.79
setting
setting
0 (initial
value)
1
2
0 (initial
3, 4
value)
6
7
0
1
2
3, 4
*1
1, 2
6
7
0
1
2
*1
10, 12
3, 4
6
7
*1
Use Pr.340 = "2 or 12" setting to perform communication with the RS-485 terminals. Even if an instantaneous power failure occurs while Pr.57
Restart coasting time ≠ "9999", the inverter continues running at the condition before the instantaneous failure. When Pr.340 = "1 or 10", if a
power failure occurs while the start signal is being input through communication, the start signal is OFF at power restoration.
*2
The operation mode cannot be directly changed between the PU operation mode and Network operation mode.
*3
Switching between the PU and NET operation modes is available with the
Parameters referred to
Pr.57 Restart coasting
timepage
Pr.79 Operation mode
selectionpage 228
238
5. PARAMETERS
5.6 (D) Operation command and frequency command
Operation mode at power-ON, at
power restoration, or after a reset
External operation mode
PU operation mode
External operation mode
External/PU combined operation mode
External operation mode
X12 (MRS) signal ON: External
operation mode
X12 (MRS) signal OFF: External
operation mode
NET operation mode
PU operation mode
NET operation mode
External/PU combined operation mode
NET operation mode
X12 (MRS) signal ON: NET operation
mode
X12 (MRS) signal OFF: External
operation mode
NET operation mode
PU operation mode
NET operation mode
External/PU combined operation mode
NET operation mode
External operation mode
446,
page 451
Operation mode switching
Switching among the External, PU, and NET operation modes is
*2
enabled.
Fixed at PU operation mode.
Switching between the External and NET operation modes is enabled.
Switching to PU operation mode is disabled.
Operation mode switching is disabled.
Switching among the External, PU, and NET operation mode is
enabled while running.
Switching among the External, PU, and NET operation modes is
*2
enabled.
Fixed at External operation mode (forcibly switched to External
operation mode).
Same as Pr.340 = "0".
Switching between the PU and NET operation mode is enabled.
Same as Pr.340 = "0".
Fixed at NET operation mode.
Same as Pr.340 = "0".
Switching between the PU and NET operation mode is enabled during
*3
operation.
Same as Pr.340 = "0".
key on the operation panel and the X65 signal.
*3