• When the motor rotation direction is restricted in Pr.78 Reverse rotation prevention selection, rotation is performed not
in the prohibited direction but in the permitted direction.
STF
Y215
Output frequency
Pr.1474
0Hz
• Use Pr.1472 Cleaning reverse rotation frequency and Pr.1474 Cleaning forward rotation frequency to set the running
frequency for cleaning operation, and use Pr.1473 Cleaning reverse rotation operation time and Pr.1475 Cleaning
forward rotation operation time to set the operating time after the cleaning running frequency is reached.
• Use Pr.1477 Cleaning acceleration time and Pr.1478 Cleaning deceleration time to set the acceleration/deceleration
time for cleaning operation.
• The Y215 signal turns ON during cleaning operation. For the Y215 signal, set "215 (positive logic)" or "315 (negative logic)"
in any of Pr.190 to Pr.196 (Output terminal function selection) to assign the function.
 Cleaning trigger selection (Pr.1471, Pr.1479, X98 signal)
• Use Pr.1471 Cleaning trigger selection to select the trigger to start cleaning operation. As set in Pr.1471, cleaning
operation is started when any of the applicable trigger conditions is satisfied.
Pr.1471
Trigger factor
setting
Bit 0
Start trigger
Bit 1
Output current
Bit 2
PID upper/lower limit
Bit 3
Load warning
X98 signal input
Time trigger
*1
The ON state at power-ON or inverter reset is not regarded as a trigger.
*2
Use Pr.150 and Pr.151 to set the detection level. (Refer to
*3
Use Pr.131, Pr.132, Pr.1143, and Pr.1144 to set the detection level. When the frequency reflection is not provided for the PID setting, or when
the function is disabled, a trigger does not occur. (Refer to
*4
Set the load characteristics fault detection function. When the function is disabled, a trigger does not occur. (Refer to
*5
The output signal can be used as a trigger if the signal is not assigned to a terminal.
*6
When the automatic restart after instantaneous power failure is set for every start, or when the online auto tuning is enabled, cleaning is started
upon completion of the set operations.
*7
While the self power management is enabled, the start trigger is disabled.
• Convert a bit image (binary) of the trigger factor into a decimal value, and set the value in Pr.1471.
bit
15
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
ON
ON
As reverse rotation is disabled (Pr.78 = "1"), forward
rotation is performed.
Value in each bit
0
Trigger disabled. Trigger enabled. Turning ON of the start command is defined as a trigger.
Trigger disabled. Trigger enabled. Turning ON of the Y12 signal is defined as a trigger.
Trigger disabled. Trigger enabled.
Trigger disabled. Trigger enabled.
7
0
1
bit 0 Start trigger
bit 1 Output current trigger
bit 2 PID upper/lower limit trigger
bit 3 Load warning trigger
Time
1
Turning ON of the FUP, FDN, FUP2, or FDN2 signal is
defined as a trigger.
Turning ON of the LUP or LDN signal is defined as a
*4*5
trigger.
Turning ON of X98 signal is defined as a trigger. (This trigger
is always enabled by assigning the X98 signal to an input
terminal.)
When Pr.1479 ≠ "0", the trigger is enabled.
page
321.)
page
401.)
Pr.1471 setting
Set the decimal converted
value of the bit image.
Remarks
*3*5
page
281.)
5. PARAMETERS
5.11 (A) Application parameters
1
2
3
4
5
6
7
8
*1*6*7
*2*5
9
10
399