Connection to a PC by Host Link via RS-232C
PC
C200HS, CQM1
C200HX/HG/HE(-Z)
CQM1H
CPM1
CPM2A, SRM1
CPM2C
34
*1
Set the Host Link baud rate to 9,600 bps or 19,200 bps with the memory
switch for the baud rate. For details, refer to Selecting the Host Link Baud
Rate (page 86).
S C-series C200HS, C200HX/HG/HE(-Z), CPM1, CPM2A, CPM2C, CQM1,
CQM1H, SRM1
The method for connecting to the CPU Unit depends on the model of PC in the
way shown in the following table.
S Connect to the CPU Unit's RS-232C port.
S Connect to the CPU Unit's RS-232C port.
S Connect to one of the RS-232C ports (port A or B) on the Communications
Board.
S Connect to one of the RS-232C ports (port A or B) on the Communications
Board.
S Connect via the CS1W-CN118 Connecting Cable using the peripheral port
S Connect to the RS-232C port (port 1) on the Serial Communications Board.
S Connect via the CPM1-CIF01 RS-232C Adapter using the peripheral port.
S Connect to the CPU Unit's RS-232C port.
S Connect via the special RS-232C Adapter (CPM1-CIF01) using the peripheral
port.
S Connect to the CPU Unit's RS-232C port or peripheral port using the
CPM2C-CN111, CS1W-CN114, or CS1W-CN118 Connecting Cable. (The
CPM2C-CN111 splits the communications port on the CPU Unit into an
RS-232C port and the peripheral port. The CPM1-CIF01 RS-232C Adapter is
also required to connect to the peripheral port.)
PC Setup Settings
When connecting to a C200HS, C200HX/HG/HE(-Z), CPM1, CPM2A, CPM2C,
CQM1, or CQM1H CPU Unit, or to the SRM1, make the following communica-
tions settings in the PC Setup.
Item
Communications
Host Link
mode
Baud rate
Set to the same baud rate as the NT30/NT30C (See note 1.)
Stop bit
2 stop bits
Parity
Even
Data length
ASCII 7 bits
Unit #
00
*1
Set the Host Link baud rate to 9,600 bps or 19,200 bps with the memory
switch for the baud rate. For details, refer to Selecting the Host Link Baud
Rate (page 86).
Make the PC Setup settings directly from the Programming Device (CX-Pro-
grammer). For details of PC Setup operations, refer to the manual for the PC
used.
The following tables give the PC Setup words and the contents of settings for
different combinations of connected model and port.
Connection Method
Contents of Settings at Host
Section
2-5