Output Current Level Setting for Multi-function Output Terminals

Settings
 When output current is higher or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, and 02-15 is set to 27).
 When output current is lower to Pr.02-33, it will activate multi-function output terminal (Pr.02-13,
02-14, and 02-15 is set to 28).

Output Boundary for Multi-function Output Terminals

Settings
 When output frequency is higher or equal to Pr.02-34, it will activate the multi-function terminal
(Pr.02-13, 02-14, and 02-15 is set to 29).
 When output frequency is lower
02-14, 02-15 is set to 30).

External Operation Control Selection after Reset and Activate

Settings
 Setting 1: in below situation, the driver will automatically run the command, please pay extra
attention
Status 1: After the drive is powered on and the external terminal for RUN keeps ON, the drive will
run.
Status 2: After clearing fault, once a fault is detected and the external terminal for RUN keeps ON,
the drive can run after pressing RESET key.
ze ro
sp eed
brak e
0~150%
0.00~599.00Hz
to
Pr.02-34, it will activate the multi-function terminal (Pr.02-13,
0: Disable
1: Drive runs if the run command still exists after reset or re-boots.
12.1-02-16
Chapter 12 Description of Parameter SettingsCP2000
A
B=A
RUN
relea se
ze ro
sp eed
STOP
brake
Tim e
Factory Setting: 0
Factory Setting: 3.00
Factory Setting: 0