Devicenet Connection Port; Address Switch; Function Switch - Delta DVPDT02-H2 Operation Manual

Devicenet slave communication module
Table of Contents

Advertisement

2.3

DeviceNet Connection Port

The connector is used on the connection to DeviceNet network. Wire by using the connector enclosed with
DVPDT02-H2.
PIN
1
2
3
4
5
2.4

Address Switch

The switch is used on setting up the node address of DVPDT02-H2 on DeviceNet network.
Switch setting
0 ~ 63
64~ 99
Example: If you need to set the node address of DVPDT02-H2 to 26, simply switch the corresponding switch
1
of x10
to 2 and the corresponding switch of x10
Note:
Please set up the node address when the power is switched off. After the setup is completed, re-power
DVPDT02-H2.
When DVPDT02-H2 is operating, changing the set value of the node address will be invalid.
Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.5

Function Switch

The switches are for:
Setting up I/O data holding function (IN0).
Setting up baud rates of DeviceNet network (DR0 ~ DR1).
DR1
OFF
OFF
ON
ON
IN0
IN1
Note:
DVP-PLC Operation Manual
DeviceNet Slave Communication Module DVPDT02-H2
Signal
Color
V-
Black
CAN_L
Blue
SHIELD
-
CAN_H
White
V+
Red
Valid DeviceNet node address
Invalid DeviceNet node address
DR0
OFF
ON
OFF
ON
Incorrect setting
When the DeviceNet connection is
OFF
interrupted, the content in the buffer area
will not be held.
When the DeviceNet connection is
ON
interrupted, the content in the buffer area
will be held.
Reserved
Contect
0 VDC
Signal-
Shielded
Signal+
24 VDC
Content
0
to 6.
Baud rate
125 kbps
250 kbps
500 kbps
5
4
3
2
1
1 0
X
1 0
X
DR 1
DR 0
IN 1
IN 0
5