Analog Input / Output Parameters - Delta CP2000 Series User Manual

Delta fan/pump vector control drive
Hide thumbs Also See for CP2000 Series:
Table of Contents

Advertisement

03 Analog Input / Output Parameters

Pr.
03-00
Analog input selection (AVI1)
03-01
Analog input selection (ACI)
03-02
Analog input selection (AVI2)
03-03
Analog input bias (AVI1)
03-04
Analog input bias (ACI)
Analog positive voltage input
03-05
bias (AVI2)
Positive / negative bias mode
03-07
(AVI1)
Positive / negative bias mode
03-08
(ACI)
Positive / negative bias mode
03-09
(AVI2)
Analog frequency command for
 03-10
reverse run
03-11
Analog input gain (AVI1)
03-12
Analog input gain (ACI)
03-13
Analog input gain 1 (AVI2)
03-14
Analog input gain 2 (AVI2)
03-15
Analog input filter time (AVI1)
03-16
Analog input filter time (ACI)
03-17
Analog input filter time (AVI2)
Addition function of the analog
03-18
input
Signal loss selection of
03-19
analog input 4~20mA
Explanation
Chapter 11 Summary of Parameter SettingsCP2000
Settings
0: No function
1: Frequency command (speed limit under torque
control mode)
4: PID target value
5: PID feedback signal
6: PTC thermistor input value
11: PT100 thermistor input value
13: PID offset amount
-100.0~100.0%
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving
as the center
4: Serve bias as the center
0: Negative frequency is not valid. Forward and
reverse run is controlled by digital keypad or external
terminal.
1: Negative frequency is valid. Positive frequency =
forward run; negative frequency = reverse run.
Direction cannot be switched by digital keypad or
external terminal control.
-500.0~500.0%
0.00~20.00 sec.
0: Disable (AVI1, ACI, AVI2)
1: Enable
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0Hz
3: Stop immediately and display ACE
11-17
Factory
Setting
1
0
0
0.0
0
0
100.0
0.01
0
0

Hide quick links:

Advertisement