Terminal Counting Value Attained (Return To 0); Preliminary Counting Value Attained (Not Return To 0) - Delta CP2000 Series User Manual

Delta fan/pump vector control drive
Hide thumbs Also See for CP2000 Series:
Table of Contents

Advertisement

bit setting
bit15 bit14 bit13 bit12 bit11 bit10
MO20 MO19 MO18 MO17 MO16 MO15 MO14 MO13 MO12 MO11 MO10 Reserved

Terminal Counting Value Attained (return to 0)

Settings
 The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23). Upon
completion of counting, the specified multi-function output terminal will be activated
(Pr.02-13~02-14, Pr.02-36, 02-37 is set to 18). Pr.02-19 can't be set to 0.
 When the display shows c5555, the drive has counted 5,555 times. If display shows c5555, it
means that real counter value is between 55,550 to 55,559.

Preliminary Counting Value Attained (not return to 0)

Settings
 When the counter value counts from 1 and reaches this value, the corresponding multi-function
output terminal will be activated, provided one of Pr. 02-13, 02-14, 02-36, 02-37 set to 17
(Preliminary Count Value Setting). This parameter can be used for the end of the counting to
make the drive runs from the low speed to stop.
Di spl ay va lu e
[00 -04 =0 1]
[02-06=23]
TRG
Counter Trigger
( ou tpu t sig na l)
P re li min ar y Cou nte r V al ue
RY 1 P r.0 2- 13 =17
Te rmi na l Co un ter Va lu e
RY 2 P r.0 2- 14 =18
Desired Frequency Attained 1
Desired Frequency Attained 2
Settings
The Width of the Desired Frequency Attained 1
The Width of the Desired Frequency Attained 2
Settings
 Once output frequency reaches desired frequency and the corresponding multi-function output
terminal is set to 3 or 4 (Pr.02-13, 02-14, 02-36, and 02-37), this multi-function output terminal will
be OFF.
bit9
0~65500
0~65500
02 -13, 02- 14, 0 2-3 6, 02 -37
02 -14=1 7
0.00~599.00Hz
0.00~599.00Hz
12.1-02-14
Chapter 12 Description of Parameter SettingsCP2000
bit8
bit7
bit6
bit5
02 -20=3
02 -19=5
bit4
bit3
bit2
bit1
RY3
RY2
Factory Setting: 0
Factory Setting: 0
1.0msec
1.0msec
Th e wi dth of tr ig ge r si gn al
Factory Setting: 60.00/50.00
Factory Setting: 2.00
bit0
RY1