Environment
Noise immunity
Operation/storage
Vibration/shock
immunity
8-8-4 Installation
Connecting CMC-EIP01 to Network
1. Turn off the power of AC motor drive.
2. Open the cover of AC motor drive.
3. Connect CAT-5e network cable to RJ-45 port on
CMC-EIP01 (See Figure 2).
RJ-45 PIN Definition
PIN
Signal
1
Tx+
2
Tx-
3
Rx+
4
--
8-8-5 Connecting CMC-EIP01 to VFD-CP2000
1. Switch off the power of AC motor drive.
2. Open the front cover of AC motor drive.
3. Place the insulation spacer into the positioning pin at Slot 1 (shown in Figure 3), and aim the
two holes on the PCB at the positioning pin. Press the pin to clip the holes with the PCB (see
Figure 4).
4. Screw up at torque 6~8 kg-cm / [5.21~6.94 in-lb.] / [0.6~0.8Nm] after the PCB is clipped with the
holes (see Figure 5).
ESD (IEC 61800-5-1,IEC 61000-4-2)
EFT (IEC 61800-5-1,IEC 61000-4-4)
Surge Test (IEC 61800-5-1,IEC 61000-4-5)
Conducted Susceptibility Test (IEC 61800-5-1,IEC 61000-4-6)
Operation: -10°C ~ 50°C (temperature), 90% (humidity)
Storage: -25°C ~ 70°C (temperature), 95% (humidity)
International standard: IEC 61800-5-1, IEC 60068-2-6/IEC 61800-5-1, IEC 60068-2-27
Definition
PIN
Positive pole for
data transmission
Negative pole for
data transmission
Positive pole for
data receiving
N/C
Signal
Definition
5
--
N/C
Negative pole for
6
Rx-
data receiving
7
--
N/C
8
--
N/C
8-21
Chapter 8 Option CardsCP2000
[Figure 2]