ABB ETL600 Instruction Manual page 362

Digital power line carrier system
Table of Contents

Advertisement

Revision:
A
2.4
Firmware download parameters
The Firmware download dialog box contains a field with download parameters. You can choose
either an automatic firmware download or a user controlled firmware download by deactivating the
check box.
2.4.1
Automatic firmware download
This is the recommended method to download the firmware. The HMI600 executes all necessary
actions for a proper operation. The checkbox Automatic firmware download has to be checked.
The download process compares the firmware version on the modules with the firmware version of
the selected download files. The download to a module is not executed if the versions are equal.
So only the modules are modified, which have not the same version as the selected download files.
2.4.2
User controlled firmware download
Note:
The user controlled firmware download gives you the opportunity to modify one selected module in
a system. Deactivating the checkbox for automatic firmware download enables the button Reset
system. Please follow the instruction in the "Download status & progress instruction" window.
3
Firmware download
3.1
Update of non-configured equipment
1.
On the File menu click Open. This opens the Open dialog box. Select the configuration file
and click Open.
2.
From the Equipment menu click Connect. This opens the Connect dialog box.
3.
Click Read & Write access.
4.
Click OK.
5.
On the Equipment menu, click Commissioning and maintenance and then click Firmware
download...
6.
In the following message box click Yes if you are aware of a malfunction of the PLC link. This
opens the Firmware download dialog box. Otherwise click No.
7.
The checkbox Automatic firmware download has to be checked.
8.
Click Start firmware download to start the operation.
9.
The following message box informs you which download files are used. Be sure that all files
are from the same release directory.
Click Yes to accept these files. This starts the firmware download. The HMI600 automatically
performs the update and resets the system after the update is completed.
Click No to select other files. This opens a file open dialog box for each kind of download file.
Click Cancel to stop firmware download.
10. Wait until the Close button changes to the active state.
11. Click Close to leave the firmware download dialog box.
12. From the Equipment menu, click Download configuration. The license is checked and an
error message appears if it is not sufficient. Compatibility checks are performed to verify that
the firmware versions on the different modules in the equipment belong to the same release
as the HMI600. If not, an error message pops up. Depending on the message, an earlier
version of HMI600 must be used and/or the firmware of some modules must be upgraded.
13. If the Download configuration operation is possible, a message box appears, which informs
you that the link will be cut off for a few seconds.
Click Yes.
Language:
EN
Only for authorized and properly trained persons.
Page:
1KHW001496-EN
4/7