G4AI detail warnings

HMI600 Alarm Text
• Active configuration
not stored to
EPROM
9.6.4.

TDM Bus communication alarms and warnings

In addition to the alarms and warnings listed in the previous tables, HMI600 reports
separately the following TDM bus errors and warnings:
HMI600 Alarm Text
Error
communicating with
slot N...
Error on board at
slot N...
Warning on board at
slot N...
9.7.

Replacement of faulty items

Modules may only be replaced by properly trained personnel
authorized to do so. Strictly observe the safety instructions at the
beginning of this section.
Modules may not be withdrawn or inserted while the equipment is in
operation. Switch off the power supply and disconnect external cables
first.
As stated earlier, replacement of faulty items can be done only at
module level and not component level since surface mount technology
is used for components of most of the modules. While replacing a
faulty module with a new module, ensure that the fault is not due to
some incorrect external wiring or mode of operation. Else even the
new module will go faulty. Remember to program correct jumpers /
strapping on the new module before replacement.
Troubleshooting
1KHW001489-EN
Explanation and corrective actions
(the latter in italics)
A test configuration for the board is active which will be
lost when the associated test configuration timer runs out.
Store the configuration to EPROM, stopping the test
configuration
timer,
overwriting the test configuration timer.
Explanation and corrective actions
(the latter in italics)
TDM bus communication with the board at slot N... is
disturbed.
Make sure that the correct type of board is firmly plugged in
at slot N... Unplug the board at slot N... and check if all pins
of the connector to the backplane are present and not bent.
An alarm is present on the board at slot N...
Check the status of the board at slot N... for detailed
information.
A warning is present on the board at slot N...
Check the status of the board at slot N... for detailed
information.