to send the configuration commands to the modem. As these
commands differ depending on the type of the modems used, it is not
possible to specify a common configuration sequence for all modem
types. Please refer to your modem dealer or the example below for
further information.
Example:
Configuration of a ZyXEL U-90E Modem for connection to P4LT:
The modem is to be configured to the settings given by column
'Modem at P4LT' of the previous table with the help of the program
HyperTerminal. Connect the modem to one of the COM-ports of the
PC with a 9 pole 1:1 modem cable (female to male). In case the COM
port of the PC has a 25 pole RS-232 connector, an adapter (25 pole
female to 9 pole male) is needed. Start hyperterminal, select the
correct COM port and set the Baudrate to 57'600 Bd, connect to the
modem and type at. The modem should answer with OK. If your
modem returns garbage characters, retype at to adapt the modems
autobaud function to your baud rate. Do not send any other characters
(e.g. return) before at. This may disturb your modems autobaud
functionality. If you don't get any answer check your connections, the
modem settings and try again.
Now enter the following commands to setup the modem: The modem
should always send OK to confirm your entry.
Command:
atz4
ate0
ats0=1
ats20=3
ats15=8
at&w0
atz0
4.4.3.2.2.

Configuration of HMI600

In the dialog box Options / Communications..., select Phone
modem, choose the correct Modem and set the Timeout to 3500ms
or higher.
User Interface Program
1KHW001489-EN
Explanation:
Load factory settings to get a defined modem setting.
Command echo off //delete.
Set the number of rings on which the modem will answer
automatically. S0=0 disables the auto answer.
Sets the speed of the serial interface to 57'600.
Set the modem to even parity and a character length of 11
(1 start bit , 8 data bits, 1 parity bit, 1 stop bit). The
terminal program now might receive some garbage
characters, which can be ignored.
Change the communication settings of the PC to the
modem using Settings / Control panel / Modems and of
hyperterminal to 57'600 Baud, 8 bits, even parity, 1 stop
bit. When typing at, the modem should answer with OK.
Save the settings to profile 0.
Load profile 0 and set profile 0 as power-on profile.