Configure Teleoperation Port Used For Transit Operation - ABB ETL600 Instruction Manual

Digital power line carrier system
Table of Contents

Advertisement

ETL600
9. Select the Output level for your application. It is the input level of
the external device connected to the port.
10. You should also check all other signals present at the output in the
list named ' Signals after selected filter ' of the ' Output '-sheet.
The HMI600 calculates the Max. output level and compares it with
the max. output level of the teleoperation port. However, you
should also check the input capability of your external device.
If the Max. output level is too high, you have two possibilities to
solve the problem. Either you reduce the output level or you insert
an appropriate output filter at this output port to filter away some of
the signals, thus reducing the number of signals to be checked in
the list ' Signals after selected filter' of the 'Output' -sheet.
11. Click Finish .
Configure an input and/or an output filter, if necessary:
From the sheet 'Configure Teleoperation, ext. teleprotection ':
12. For an input filter, press the button Select filter in section Input
filter .
13. Select Standard transit filter for a filter without group delay
equalization or select Special transit filter for a filter with group
delay equalization.
14. Select the frequency range of the filter.
15. Click OK .
To configure an output filter, repeat steps 12 to 14 except that the
button Select filter to be pressed in step 12 is in section output filter
instead of section input filter .
From the sheet ' Configure Teleoperation, ext. teleprotection ':
Configure all other teleoperation ports:
16. Repeat configuration steps 1 to 14 for all other teleoperation ports
17. Close the sheet 'Configure Teleoperation, ext. teleprotection' by
clicking OK.
5.3.4.4.

Configure teleoperation port used for transit operation

The procedure of configuration is very similar to the procedure
explained above.
Switch a port on:
1. Select the port you want to configure.
2. If the service(s), which run(s) over the port, can be interrupted
when a teleprotection command is transmitted or received locally,
click On – disconnectable . In case the services mustn't be
interrupted
On - non disconnectable .
Note:
Configuration and Set-up
1KHW001489-EN
by
a
teleprotection
You have to consider all services routed via this port.
If a teleprotection system is configured at this
equipment and the transit port is configured as
On - disconnectable , all services routed via this port
are interrupted!
ABB Switzerland Ltd
command,
November 2005
click
5-21