Aplc Channels 1, 2 And 3; Internal Teleprotection - ABB ETL600 Instruction Manual

Digital power line carrier system
Table of Contents

Advertisement

ETL600
- select Up to 2 V.11 / up to 6 V.24, if in slot N45 a P4LU board
(with piggyback module) is to be inserted.
In the frame MUX600 terminal multiplexer,
- Check the box DPLC channel multiplexing, if several data
channels have to be multiplexed for transmission via the DPLC
channel.
- Check the box V.24 port sharing, if several V.24 ports have to
be connected to the same data channel. This works only if not
more then one of the data terminals connected to these ports is
generating data at any time.
In the frame NSK600 modems, the available NSK600 modems
(up to 2 or 4 depending on the entry in the frame Data ports) can
be associated to the configured APLC channels.
5.3.1.3.

APLC channels 1, 2 and 3

The tabs APLC channel 1, APLC channel 2, APLC channel 3 are
only shown if these channels have been configured (refer to section
5.3.1.1). For each of the configured channels,
In the frame Telephony,
- select the telephony operation mode as described in section
5.3.4.1;
- select Up to 2 V.11 / up to 6 V.24, if in slot N45 a P4LU board
(with piggyback module) is to be inserted.
In the frame Teleoperation,
- select the Number of ports that have to be supported.
In the frame External Teleprotection,
- check the box External Teleprotection available, if such a
5.3.1.4.

Internal teleprotection

In the frame Channel allocation, select the number of
Teleprotection devices (TPE). Depending on the settings in the
Type tab, one or two internal TPE can be activated.
In the frame Teleprotection ports TPE1, enter the number of
required in- and outputs of TPE1.
In the frame Teleprotection ports TPE2, enter the number of
required in- and outputs of TPE2.
Note:
Configuration and Set-up
1KHW001489-EN
device (e.g. NSD570) is to be conncted to the ETL600.
The number of required Teleprotection Interfaces
type G4AI is determined by the HMI600 using the
following rules:
• Each interface provides four inputs and four solid
state outputs (maximum 28 when no other
modules are plugged in the channel rack).
• Each
interface
provides
November 2005
ABB Switzerland Ltd
two
relay
outputs
5-15