Tpe Warnings; G4Ai Detail Hardware Alarms - ABB ETL600 Instruction Manual

Digital power line carrier system
Table of Contents

Advertisement

ETL600
HMI600 Alarm Text
• Max Rx command
duration exceeded
• G4AI interfac
e alarm At l
9.6.3.4.
T
PE warning
HMI600 Alarm Text
• Active configuration
not stored to
EPROM
• Local test loop
active
• Loop test failed
once or twice
• Test signal
transmitted or
received
• G4AI warning
9.6.3.5.
G4AI detail hardware a
HMI600 Alarm Text
• Tx single
component failure at
input 1-4
Troubleshooting
1KHW001489-EN
Explanation and corrective actions
(the latter in italics)
A command has been received of duration longer than the
configured maximum (e.g. Configuration / NSD600 /
Alarm TPE1 / Command outputs during link failure )
ha
s been exceeded.
east one of the interfaces connected to G4AI caused
an alarm.
Check G4AI status for detailed information.
s
Explanation and corrective actions
(the latter in italics)
A test
configuration for TPE is active which will be lost
when
the associated test configuration timer runs out.
Store
the configuration to EPROM, stopping t
configuration
timer,
overwr
iting the test configuration.
Local test lo
op is active for TPE (e.g. Equipment / Tuning
esting / Test internal teleprotection ).
a
nd T
The next cyclic loop test will be sent within 5 minutes
A TPE test signal has been transmitted or received.
A warn
ing is present on at least one of the G4AI boards.
Check
G4AI status for detailed information.
larms
Expla
nation and corrective actions
(the
la
tter in italics)
One c
omponent of the redundant circuitry of a command
input i
s faulty.
Replace the
faulty G4AI board.
November 2005
ABB Switzerland Ltd
or
reset
the
system,
he test
thereby
9-27