ABB ETL600 Instruction Manual page 320

Digital power line carrier system
Table of Contents

Advertisement

ETL600 System Test Report
Test
No.
Test procedure
B.10.8
Pax 4/2-wire
Test E-Wire:
Close and open at
Remote equ. at terminal,
telephony 4a-4b
Measure Output level of
AF1.
Feed 800 Hz with
configured input level of
remote PAX (Def.:
-3.5 dBm).
Activate at terminal,
telephony 4a-4b on both
equ..
Measure Output level of
PAX2W.
Feed 800 Hz with
configured input level of
remote PAX (Def.:
-3.5 dBm).
(Activate at terminal,
telephony 4a-4b on both
equ.)
Test Local/Transit:
Measure Output level at
AF1.
Feed 800 Hz with
configured input level of
remote PAX2W (Def.:
-0.0 dBm).
Activate at terminal,
telephony 5a-4b of
remote equ..
(Activate at terminal,
telephony 4a-4b on both
equ.)
PAX-BLOCKING normal Measure at terminal,
PAX-BLOCKING
blocked
Switch off remote equ.,
wait about 30 sec.
© ABB Switzerland Ltd
Revision:
_
Test point
Mark if configured:
Terminal, telephony
3a-3b
Feed into rem. equ. at
terminal, telephony
1a-1b
Measure at terminal,
telephony 2a-2b
Feed into rem. equ. at
terminal, telephony
1a-1b
Measure at terminal,
telephony 8a-8b
Feed into rem. equ. at
terminal, telephony
8a-8b
Measure at terminal,
telephony 8a-8b
telephony 6a-6b, 6b-7a
Measure at terminal,
telephony 6a-6b, 6b-7a
Language:
Page:
EN
B8/B11
Permissible
value
Units
E-Wire must
toggle
Configured Output
dBm
(600 Ω)
level ±1 dB
(Def.: -3.5 dBm)
Configured Output
dBm
(600 Ω)
level ±1 dB
(Def.: -7.0 dBm)
Configured Output
dBm
(600 Ω)
level ±1.5 dB
(Def.: -7.0 dBm)
6a-6b is open
6b-7a is closed
6a-6b is closed
6b-7a is open
HE
Test
result
N11
N22
N54
[ ]
[ ]
N11
N22
N54
[ ]
[ ]
N11: ___________
N22: ___________
N54: ___________
N11: ___________
N22: ___________
N54: ___________
N11: ___________
N22: ___________
N54: ___________
N11
N22
N54
[ ]
[ ]
N11
N22
N54
[ ]
[ ]
Form 1KHW001493-EN
[ ]
[ ]
[ ]
[ ]
Rev. A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents