6.10 Commission Power Supply Unit Status Channels

Note: The PSU Status Inputs do not need to be used to monitor the power supplies if this function is not
required. They can also be configured to be used as Global Acknowledge, Global Reset or Global Inhibit.
1. If not already logged in, login with a valid administrator level user name
2. From the System Status screen select the Extras icon then System Configuration
3. Re-enter the password and press Login
4. Select System Setup
5. The screen will show the system setup tree listing of all installed I/O modules, PSU Status Inputs and
Control Centre Board(s)
6. Select a Power Supply Unit Status channel, press the Menu icon and select Commission Channel
7. Select the required parameters usijng the table below
Parameter Name
Power Supply Unit Tag
Event Type
Channel Type
Default State
Input Latch
6.11 Redundant Control Centre Board Configuration
To access the Control Centre Board configuration:
1. If not already logged in, login with a valid administrator level user name
2. From the System Status screen select the Extras icon then System Configuration
3. Re-enter the password and press Login
4. Select CCB Management then CCB Configuration
Access Level: Administrator
Parameter Name
Default Setting
CCB Redundancy
Single CCB
Mode
6. Commissioning
Default Setting
Value Range
PSU 1 Alarm
30 characters
PSU 2 Alarm
PSU 3 Alarm
PSU 4 Alarm
Alarm
Alarm, Fault, Warning
Normal PSU
Ack Global, Reset Global, Inhibit Global
NO for Standard /
Normally Closed (NC),
NC for Safe
Normally Open (NO)
Non-Latching
Non-Latching, Latching
Value Range
Single CCB / Dual CCB
Comment
Only needs to be changed if a redundant CCB has been
added or removed
86
Touchpoint Pro
Operating Instructions
Comment