14. Appendix 1 - Modbus Option
The data value for each register can be one of the following:
Value
Status
0
Channel operating normally
1
RATE alarm active
2
LTEL alarm active
3
STEL alarm active
4
A1 alarm active
5
A2 alarm active
6
A3 alarm active
7
Fault active
8
Inhibit active
9
Not used
10
Not used
11 or higher
No data available
14.6 Register Allocation for Function 03 / 06 / 16 – Read / Write
Holding Registers
All registers use 16 bit data words.
The Channel Type field identifies the channel as Input or Output. The decimal value 105 (= ASCII "i") is used
for Inputs, the decimal value 111 (= ASCII "o") for Outputs. The decimal value 6 together with channel ID 0
is used for master commands. Function 16 can be used to write to the 40n01 to 40n04 and 41n01 to 41n05
(n = 0 to 9) ranges of registers only.
Caution: When using Function 6 or Function 16, ensure that the registers related to the command
are completely filled before setting the Block Active flag, otherwise an unintended command may be
performed.

14.6.1 Query Poll Registers

Query Poll Block
Block Active
1
40001
2
40101
3
40201
4
40301
5
40401
6
40501
7
40601
8
40701
9
40801
10
40901
Channel Type
Channel ID
40002
40003
40102
40103
40202
40203
40302
40303
40402
40403
40502
40503
40602
40603
40702
40703
40802
40803
40902
40903
188
Query Type
Result
40004
40005
40104
40105
40204
40205
40304
40305
40404
40405
40504
40505
40604
40605
40704
40705
40804
40805
40904
40905
Touchpoint Pro
Operating Instructions
Result String
40006 to 40036
40106 to 40136
40206 to 40236
40306 to 40336
40406 to 40436
40506 to 40536
40606 to 40636
40706 to 40736
40806 to 40836
40906 to 40936