15. Appendix 2 - Configurable
Parameter Reference Guide

15.2.6 Suppression Settings

Access Level: Engineer
Parameter Name
Zero Suppression Positive
Zero Suppression Negative
Note: Trend logging takes place when the value of an input channel changes. The system will not log values
while they remain within the zero suppression limits.
Note: If a threshold alarm level is set within the zero suppression band, no alarm signal will be generated.
15.2.7 Threshold Alarm 1 Settings
Access Level: Engineer
Parameter Name
Default Setting
Alarm 1 Enable
Enabled
Alarm 1 Level
20 %FSD
Alarm 1 Trigger
Rising
Alarm 1 Latch
Latching
15.2.8 Threshold Alarm 2 Settings
Access Level: Engineer
Parameter Name
Default Setting
Alarm 2 Enable
Enabled
Alarm 2 Level
50 %FSD
Alarm 2 Trigger
Rising
Alarm 2 Latch
Latching
15.2.9 Threshold Alarm 3 Settings
Access Level: Engineer
Parameter Name
Default Setting
Alarm 3 Enable
Enabled
Alarm3 Level
75 %FSD
Alarm3 Trigger
Rising
Alarm3 Latch
Latching
Default Setting
Value Range
0
0.0 to 25.0 %FSD
0
0.0 to -25.0 %FSD
Value Range
Enabled / Disabled
According to sensor range
Rising / Falling
Non-Latching / Latching
Value Range
Enabled / Disabled
According to sensor range
Rising / Falling
Non-Latching / Latching
Value Range
Enabled / Disabled
According to sensor range
Rising / Falling
Non-Latching / Latching
Comment
The gas concentration shall be set to 0.0 when the gas
concentration value received from the sensor is between
the "Zero suppression Positive" and "Zero suppression
Negative" values.
203
Touchpoint Pro
Operating Instructions