MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
8. Maintenance
1. If not already logged in, login with a valid engineer level user name
2. From the System Status screen select the Inputs icon then select the channel to be calibrated
3. From the popup menu, select Inhibit to inhibit the channel
Figure 8.7 Inputs Screen with menu options
4. Select Calibration from the popup menu
Figure 8.8 Calibration Screen
5. Select Zero Adjust, and when ready press OK and apply clean air to the sensor
6. View the reading until it is stable, and then press Accept
124