15. Appendix 2 - Configurable
Parameter Reference Guide

15.2.3 Sensor Settings

Access Level: Administrator
Parameter Name
Default Setting
Gas Name
"Gas"
Gas Unit
"%FSD"
Bridge Current
200 mA
15.2.4 Range Settings
Access Level: Administrator
Parameter Name
Default Setting Value Range
Signal Range Min
0
Signal Range Max
100
Gas Range Min
0
Gas Range Max
100
15.2.5 Display Settings
Access Level: Administrator
Parameter Name
Peak Hold Enable
Note: The number of decimal places to be displayed is determined by the Gas Range Max setting as follows:
This is also the resolution at which data will be logged for the trend report.
Value Range
Maximum 10 Alphanumeric Characters
%FSD, % Vol., ppm, ppb, mA, mV, mg/
m3, LEL.m or maximum 5 Alphanumeric
Characters
180 to 360 mA
0 mV to 100 mV
5 mV to 300 mV
Sensor / Unit specific
Sensor / Unit specific
Default Setting
Value Range
Enabled
Enabled / Disabled
Gas Range Max
≥ 100
≥ 10 and < 99
< 10
Comment
FSD – Full Scale Deflection
LEL – Lower Explosive Limit
LEL.m – LEL metres
Comment
X1 = Signal Range Min (Electrical Input from Sensor)
X2 = Signal Range Max (Electrical input from Sensor)
Y1 = Gas Range Min
Y2 = Gas Range Max
Gas concentration (y) is calculated as follows:
y = (((Y2-Y1)/(X2-X1))*(x-X1))+Y1
Note: Signal Range Min and Max are over-written
during calibration, and are then no longer editable
Comment
If Peak Hold is enabled and the gas reading rises
above the configured full scale value, the channel
will display the maximum gas reading that has
been measured until it is reset
Decimal Places
0
1
2
202
Touchpoint Pro
Operating Instructions