4.8.6 Digital Input Module

Note: Channel wiring is from left to right for terminals on the top and bottom of the module. It is not
possible to move a plug from top to bottom of a module after wiring.
Please ensure correct wiring by system verification tests. See Commissioning, First Time Switch On, and
Maintenance, Testing the Touchpoint Pro System.
DIMs have two modes of operation. A DIM channel may be configured to generate an alarm, fault or
warning signal when activated.
Alternatively, a DIM channel may be configured to provide remote control of a selected group of one or
more input / output channels. The DIM may be used to remotely reset, inhibit, or acknowledge the selected
channels. When used for inhibit, repeated activation toggles the inhibit state of the selected channels.
Terminal Identification
1
2
3
4
5
6
7
8
9
10
11
12