Query Types Available - Honeywell touchpoint Pro Operating Instructions Manual

Hide thumbs Also See for touchpoint Pro:
Table of Contents

Advertisement

MAN0923_Issue 3_04/15
14. Appendix 1 - Modbus Option
Allowed values for the Result register 40n05 (n = 0 to 9)
Value
Meaning
0
Success
1
Command not permitted
2
Inter process communication failure
67
Failure

14.6.2 Query Types available

Poll No
Description
02
Read System Label
39
Read Alarm 1 level
40
Read Alarm 2 level
41
Read Alarm 3 level
42
Read STEL level
43
Read LTEL level
44
Read Rate level
102
Read Gas Name
103
Read Channel Tag Name
104
Read Gas Unit
Response formats for the Result String registers 40n06 - 40n36 (n = 0 to 9)
Type
Format
A
Float (4 Bytes – 32 bit floating point)
B
Unicode String – 35 (Unicode chars) + 1(null)
Example: Read Alarm 1 level (Query Type)
Register
Block
Channel Type
Active
(40n02)
(40n01)
Value
1
105
If Block Active is set to 1, the Controller processes the request. If Block Active is set to 0 the Controller will
not process the request or has already processed the request.
The options for Channel Type are 105 – Input Channel and 111 – Output Channel.
Response Format
B
A
A
A
A
A
A
B
B
B
Channel ID
Query Type
(40n03)
(40n04)
2
39
189
Result (40n05)
Result String (40n06 to
40n36)
(Updated upon request
(Updated upon request
execution)
execution)
Touchpoint Pro
Operating Instructions