MAN0923_Issue 3_04/15
Touchpoint Pro
Operating Instructions
4. Electrical Installation
The UPS is shipped with the following default settings. Before making connections, confirm that the
settings are as follows:
1. Buffer time limiter switch is set to "infinity" position
2. Buffer voltage switch is set to 24V
3. Battery size switch (on the side of the UPS) is set to >10 Ah
Note: If the UPS Module with battery backup option is being used, ensure that the power supply output
voltage is adjusted to at least 26 Vdc to ensure sufficient charging of the battery. To adjust the voltage,
locate the potentiometer labelled 24-28 Vdc on the front of the power supply, and adjust it using a cross
headed screwdriver.
WARNING
When handling the batteries, take great care not to connect the terminals together, e.g. by a tool
such as a screwdriver.
Note: The maximum cable length between the Touchpoint Pro Battery Box and the Touchpoint Pro System
UPS is 5 m. Wire size must be 4 mm
.
2
1. Confirm that the batteries are connected as shown below:
56