Honeywell touchpoint Pro Operating Instructions Manual page 139

Hide thumbs Also See for touchpoint Pro:
Table of Contents

Advertisement

MAN0923_Issue 3_04/15
Error
Message
Code
70
Cannot clear Inhibit because
the channel has been inhibited
automatically
71
Cannot reset because the {0} is still
active (where {0} is alarm, fault or
warning)
72
Cannot reset all events for this
channel because one or more events
are still active
73
Replace operation cannot be
performed; module type of new
module is not compatible.
74
Not used
75
Not used
76
Not used
77
Not used
78
Not used
79
The Input Module cannot be
commissioned: The maximum
number of 16 Input Modules has
already been commissioned on the
system.
80
The Output Module cannot be
commissioned: The maximum
number of 32 Output Modules has
already been commissioned on the
system.
81
Invalid test sequence
82
The user could not be added;
invalid user name. Please choose a
different user name and try again.
9. Problem Solving
Possible Cause
A mV input channel has
not yet been calibrated
or channel configuration
was interrupted, or the
inhibit delay time is
active, or the sensor/
transmitter is signalling
inhibit
The field device is still
signalling an active
alarm, fault or warning
Some alarms, faults or
warnings on the channel
have been reset, but
others are still active
Replacement module
is incorrect type or not
recognised by the CCB
Touchpoint Pro has a
maximum capacity of
16 Input and 32 Output
Modules
Please refer to error 79
CCB receives wrong Test
sequence for Relay tests
The user name must be
4 to 20 characters long
139
Remedial Action
1. For a mV channel, calibrate the channel (see
Commissioning, Calibrating a mV input channel).
2. If this is not the cause, go to System
Configuration, then System Setup.
3. Select the module with the inhibited channel, and
select Normal State.
4. If this is not successful, go to Extras then Event
History to check if an Inhibit Delay Time is active. The
inhibit condition will clear after the Delay Time has
expired.
5. If there is no Delay Time active, then investigate
the conditions at the sensor/transmitter.
Investigate the conditions at the field device.
Investigate the conditions at the field device.
1. Check and confirm that the replacement module is
of the correct type.
2. Re-initialise the ring network and try again.
3. If the error persists, update the CCB firmware.
4. If the problem persists, please contact your local
service representative.
If more channels than 64 inputs and 128 outputs
are required an additional Touchpoint Pro system is
needed. Contact your local representative to discuss
your requirements
Please refer to error 79
Please refer to error 2
Please choose a user name that meets the
requirements and try again
Touchpoint Pro
Operating Instructions