15. Appendix 2 - Configurable
Parameter Reference Guide

15.3.3 Alarm Settings

Access Level: Engineer
Parameter Name
Default Setting
Input Latch
Latching
Event Type
Alarm
15.3.4 Remote Interaction Settings
Access Level: Engineer
Parameter Name
Remote Reset Enable
Remote Inhibit Enable
Remote Acknowledge Enable Disabled
If none of the remote interaction settings are enabled, the digital input is treated as a Threshold Alarm 1 in
the Cause and Effect matrix.
15.3.5 Remote Group Interaction Settings
Access Level: Engineer
If any of the remote interaction options are enabled above, select Add / View Group Member to choose
the channels to associate with the Reset, Inhibit or Acknowledge action.
Channels can be assigned to more than one interaction group.
A DIM channel assigned to carry out a remote interaction is not available to take part in any other
interaction group.
Remote reset should not be used for catalytic sensors, since gas could still be present even
though the sensor reading has dropped. Conditions at the field device should always be
Value Range
Non-Latching / Latching
Alarm, Fault, Warning
Default Setting
Value Range
Disabled
Enabled / Disabled
Disabled
Enabled / Disabled
Enabled / Disabled
WARNING
investigated before resetting an alarm.
Comment
Comment
The digital input can be used to reset latched alarm
conditions or latched output channels.
The digital input can be used to inhibit input- or output
channels.
The digital input can be used to acknowledge alarm
conditions.
208
Touchpoint Pro
Operating Instructions