SEC-H-602 AND SEC-H-616 SECURITY CONTROLLER

Digital Input

The security controller has three (3) digital inputs, located
on a 4-position connector next to supervised input
connector (see Fig. 4 on page 11). Under the connector,
terminals are labeled GND, DI1, DI2, DI3. This means
when wiring, as many as three conductors can be landed
to the common GND terminal.
SEC-ENC-H-2
ENCLOSURE
FOR SECURITY
CONTROLLER
TAMPER
SWITCH
NC OR NO
NOTE: The WEBs-AX Security Application is pre-
configured to support the following connec-
tions:
DI1 — Tamper switch (typically for enclosure
door)
DI2 — Battery status bad (if contacts avail-
31-00012—03
4-POSITION
CONNECTOR
FOR DIGITAL
INPUTS
SHIELDS
Fig. 12. Digital input wiring example to Security Controller.
Each digital input can monitor dry contacts, either
normally-open (N.O.) or normally-closed (N.C.). All three
inputs are unsupervised—no end-of-line resistors are
required. Figure 12 below shows example wiring to all
three digital inputs of the security controller.
SECURITY
CONTROLLER
TAPE BACK SHIELD
AT DEVICE CONTACT
END (TYP).
NC
OR
AC POWER FAIL
NO
NC
OR
BATTERY STATUS BAD
NO
able)
DI3 — AC power fail (if contacts available)
Depending on the installation, not all DIs may
require connection. In almost all cases, input
DI1 is wired to the tamper switch of the
WEBs-AX Security Enclosure housing the
Security Controller.