Control settings, heating circuits
Room hook-up slope
Access
■ "Device settings"
■ "Programming"
■ "Heating circ. 1"
■ y until "Room t hook-up slope" is
highlighted
Room temperature hook-up (heating circuit)
Parameter
■ 200B - HK A1
■ 300B - HK M2
■ 400B - HK M3
Settings:
0
No room temperature hook-up
1
Room temperature hook-up only in reduced mode
2
Room temperature hook-up only in standard mode
3
Room temperature hook-up in standard and in reduced mode
Access
■ "Device settings"
■ "Programming"
■ "Heating circ. 1"
■ y until "Room t hook-up" is high-
lighted
162
(cont.)
■ l or m
■ As for heating circuit 2 and heating cir-
cuit 3
Standard setting
Setting range
This setting determines, when the room
temperature hook-up should be enabled
in addition to the weather-compensated
control.
■ l or m
■ As for heating circuit 2 and heating cir-
cuit 3
Standard setting
Setting range
10
0 to 50
3
0 to 3