Maximum flow temperature

Parameter
■ 200E - HK A1
■ 300E - HK M2
■ 400E - HK M3
Limiting the set heating circuit flow tem-
perature to a maximum value.
Access
■ "Device settings"
■ "Programming"
■ "Heating circ. 1" (heating circuit A1)
■ y to " Max. flow temp."
■ 1 or !
■ As for heating circuit 2 and heating cir-
cuit 3
Control settings, heating circuits
Note
This parameter is unsuitable for limiting
the actual flow temperature (e.g. to pro-
tect underfloor heating circuits).
Standard setting
Setting range
40 °C
10 to 70 °C