DHW control settings
Cylinder temperature DHW
Parameter
■ 6000
Switching times, DHW
Parameter
■ 6001
Min. temperature
Parameter
■ 6005
The minimum temperature prevents the
DHW temperature inside the DHW cyl-
inder from falling too low (frost protec-
tion).
Access
■ "Device settings"
■ "Programming"
■ "DHW"
■ y to"Min. temp."
■ 1 or !
Max. temperature
Parameter
■ 6006
Renewed heating will be prevented after this max. temperature has been reached
inside the DHW cylinder, until the temperature has dropped by at least 5 K.
146
Operating instructions
Operating instructions
When the actual temperature falls below
the min. temperature, the DHW cylinder
is heat up to that value plus hysteresis.
This is independent of the selected oper-
ating program.
If 2 cylinder temperature sensors are fit-
ted, only the top sensor will be used to
capture the temperature.
Standard setting
Setting range
10 °C
5 to 60 °C