Sensor Resistance Curves - Viessmann Vitocal 300-G BW Installation And Service Instructions Manual

Compact heat pump with electric drive
Table of Contents

Advertisement

Components

Sensor resistance curves

Temperature sensor
640
620
600
580
560
540
520
500
480
460
440
420
400
-40 -30 -20 -10
0
Temperature in °C
Room temperature sensors:
■ Capturing element made of "Ni 500"
■ Flow temperature sensors heating/
cooling circuit
■ Outside temperature sensor
■ Room temperature sensor
Appliance fuse protection
Note
The appliance fuse is located on PCB 1
of the message and safety components
(cross connect circuit board).
See page 61 and page 170.
Fuse F1:
■ 6.3 A slow, 250 V
■ Max. power loss ≤ 2,5 W
168
10 20 30 40 50 60
Further sensors
860
780
700
620
540
460
-20
20
60
Temperature
heat transfer medium in ºC
Further sensors:
■ Capturing element made of "Pt 500"
■ DHW cylinder sensors, top/bottom
■ Heating water buffer cylinder sensor
■ System flow sensor
■ External heat source sensor
■ All sensors are located inside the heat
pump module
Danger
Touching 'live' components can
result in the transfer of dangerous
body currents.
Before working on the equip-
ment, always ensure that the
power circuit is also at zero
volt.
Removing the fuse from the pro-
gramming unit does not switch
the power circuit to zero volt.
100
140 180

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitocal 300-g bwcVitocal 300-gwwVitocal 300-g wwc

Table of Contents