External Operating Mode Changeover Effect - Viessmann Vitocal 300-G BW Installation And Service Instructions Manual

Compact heat pump with electric drive
Table of Contents

Advertisement

System definition control settings
External operating mode changeover heating...
No. Affects the following system components
6 A1: Direct heating circuit
M2: Heating circuit with mixer, DHW heating
7 M2: Heating circuit with mixer
M3: Heating circuit with mixer
8 M2: Heating circuit with mixer
M3: Heating circuit with mixer, DHW heating
9 A1: Direct heating circuit
M2: Heating circuit with mixer
M3: Heating circuit with mixer
10 A1: Direct heating circuit
M2: Heating circuit with mixer
M3: Heating circuit with mixer, DHW heating
11 No heating circuit or DHW changeover. Only "Ext. demand" function.

External operating mode changeover effect

Parameter
■ 7012
Access
■ "Device settings"
■ "Programming"
■ "System definition"
■ y to"Op. mode change eff."
■ l or m
Standard setting
Setting range
External operating mode changeover duration
Parameter
■ 7013
136
2
0 to 3
Details in which operating mode the
components selected under parame-
ter 7011 (see previous section) are oper-
ated after an external operating mode
changeover.
Settings explained:
0 Standby
1 Reduced
2 Standard
3 Fixed value
Duration of the operating mode change-
over, even if "Party mode" is currently
enabled.
(cont.)