TTP31: SDI Fail 1 to 8

This error message appears at the central
station. The keypad at the site shows
SERVICE KEYPAD.
Procedure
Refer to
TTP30 Keypad Shows SERVICE KEYPAD
page
69.
70
Troubleshooting
TTP32: Silencing Alarms or Troubles, and
Clearing Keypad Memory
D1255 Keypad Procedures
If using a D1255 keypad that is sounding an alarm:
1. Press [Passcode][ENT] to silence the alarm.
2. Press [Passcode][ENT] again to disarm the system.
on
3. Press [Passcode][MENU/ESC] to clear keypad
memory.
4. If the point is still in an alarm condition, it shows
as faulted on the keypad. Press [NEXT] to view the
point.
If using a D1255 keypad that is sounding a trouble:
1. Press [COMMAND][4] to silence the trouble.
2. Points in trouble now appear as faulted points.
Press [NEXT] to view the points.
D1260 Keypad Procedures
If using a D1260 keypad that is sounding an alarm:
1. Press [Passcode][ENTER] to silence the alarm.
2. Press [Passcode][ENT] again to disarm the system.
3. Press [Clear display][Passcode][Clear] to clear
keypad memory.
4. If the point in alarm was a controlled point, it
appears as faulted on the keypad. Press [NEXT] to
view the point.
If the point in alarm was a 24-hour point, press
any numeric key. The keypad shows the points
that are in an alarm state.
If using a D1260 keypad that is sounding a trouble:
1. Press [Silence] to silence the alarm.
2. Press any numeric key. The keypad shows the
points that are in a trouble state.