Keypad Messages

Table 55:
Keypad Messages
System Trouble Message
9210 NOT READY
ALARM SILENCED
CALL FOR SERVICE
or
RETRIEVING PANEL
INFORMATION
CHECK DEVICE
COMM FAIL ROUTE #
EXTRA POINT 256
INVALID POINT
NO AUTHORITY
SDI FAIL #
SERVC 9210
SERVC AC FAIL
SERVC BATT LOW
SERVC BATT MSING
SERVC GROUND FAULT
SERVC PANEL
SERVC PARAM
SERVC PH LINE #1 (or 2)
SERVC PRINTER
SERVC ZONEX #
Bosch Security Systems, Inc. | 11/05 | F01U011024B
D9412GV2/D7412GV2 | Troubleshooting Guide | 4.0 Appendix
Description
The D9210B that supervises the affected access door does not have a door number
programmed into it. For troubleshooting information, refer to
Appears on Keypads When Enrolling Cards, Tokens, or Keyfobs
This message is added to the scrolling alarm message when alarm sounders are silenced. This
message clears when the [ANNUNCIATOR RESET] key is pressed.
The keypad is not receiving data from the control panel. For troubleshooting information, refer
to
TTP29 Keypad Shows CALL FOR SERVICE (D1255) or RETRIEVING PANEL
INFORMATION (D1260)
on page 67.
A point index is programmed with Display as Device set to Yes.
The control panel has made ten unsuccessful attempts to send a report to the central station
receiver.
The D9210B point does not have a point assign to it. For troubleshooting information, refer to
TTP21 Extra Points on the System
You are trying to bypass a point that is not in the same area as the scope of the keypad.
Either the function is not turned on, or the user's passcode is not authorized to perform the
function.
Devices on the SDI bus are missing:
1 to 8: keypads
17 to 19: printer modules
33 to 40: D9210B Door Access Module
80 and 88: D9133TTL-E or DX4020 Network Interface Module
A D9210B Door Access Module is programmed into the control panel, but the control panel
does not detect it. For troubleshooting information, refer to
9210
on page 18.
The AC power to the system is interrupted. Check the plug-in transformer and circuit breaker.
Pressing [TROUBLE SILENCE] silences the trouble buzz. The display clears when AC power
returns.
The system's battery has fallen below 12.1 VDC, or is temporarily draining faster than the
system can charge it.
The control panel cannot detect the battery at terminals 4 and 5.
The control panel has detected a ground fault. For troubleshooting information, refer to
Ground Fault on Control Panel
The control panel has a problem and might not be operating properly.
The telephone line is in a trouble condition. For troubleshooting information, refer to
SERVC PH LINE Appears on the Keypad
The control panel does not detect a supervised printer. Check to ensure that the printer is on,
the paper is loaded correctly, and the printer is selected.
There is a short on the zonex expansion technology. For troubleshooting information, refer to
TTP22 Keypad Shows SERVICE ZONEX
on page 60.
TTP4 Keypad Shows SERVICE
on page 95.
on page 91.
on page 62.
TTP7 D9210B NOT READY
on page 22.
TTP42
TTP40