D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0
D
E
F
Refer to the auxiliary power supply
manufacturer's troubleshooting procedures.
1.
Reconnect all negative conductors to the
auxiliary power supply's negative terminal.
2.
Connect one positive conductor to the power
supply's positive terminal, then repeat the
voltage check.
3.
Repeat this process with each positive
conductor until you identify the conductor that
causes the DVM to measure 0 VDC.
4.
Disconnect that conductor from the power
supply.
5.
Set the DVM to measure resistance.
6.
Connect the black DVM lead to the power
supply's negative terminal, and connect the red
DVM lead to the affected conductor.
Does the DVM indicate a short?
D
G
H
Figure 62: Auxiliary Power Supply Wiring Diagram
Control Panel
112
Troubleshooting
28
27
26
25
24
23
D
G
H
Refer to
TTP49 Wire Shorted to Ground
page 106.
Refer to
TTP46 Shorted Wiring
There is an open in the wiring between the auxiliary power
supply and the device or module. Refer to
Wiring
on page 100.
Device/Module
-
+
Auxiliary
Power Supply
Bosch Security Systems, Inc. | 11/05 | F01U011024B
on
on page 98.
TTP47 Open
GND
AUX