D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0
B
C
Change the setting from "I" to "D" or "blank" based
on the customer's preference.
The setting made here affects all users that
share the same authority level.
I: Users change the Master Armed state and
Perimeter Armed state to Perimeter Instant. The
armed state does not change in other areas, and
the armed state does not change if the area is
already in the Perimeter Instant or Disarmed
state.
D: Users change the local area's Master Armed
state and Perimeter Armed state to the Disarm
state. User needs access level for Master
Armed (M) or Perimeter Armed (P) state. All
areas within the scope of the keypad assigned
to the D# CC# Scope in the access handler,
and areas to which the user has disarm rights,
disarm as programmed.
Blank: Users do not have disarm rights in this
area.
Present a valid card to the reader, and open the
affected access door.
Does the alarm now occur when the total of shunt
time and extend time expires?
Call Technical Support at (888) 886-6189
for assistance.
The system is now operating as expected. If
necessary, adjust shunt and extend times to meet the
customer's preferences.
Adjust the settings for shunt time and extend time to meet
the customer's preferences, and retest.
14
Troubleshooting
Bosch Security Systems, Inc. | 11/05 | F01U011024B